SmartgridOne logo
SmartgridOne logo
Accessories
AppCertificates
Configuration from A to Z
1. Link to your account2. Accessing commissioning interface3. Grid limits4. Location / address5. Add grid energy meter6. Add other devices7. Grouping devices
8 Local Control Modes
Extra - Battery account for wear and efficiencyExtra - Battery charging scheduleExtra - Battery cost optimization settingsExtra - Battery peak shavingExtra - Device prioritiesExtra - Peak shaving plus (secondary control mode)Extra - Reactive power controlExtra - Self consumption on another meter than the grid meterFull explanationSetting control modes
Special Local Control Modes
Green certificates (Groenestroomcertificaten)Monitoring only (don't control the selected devices)Negative price wind controlPeak Shaving Relay CascadeRelay control based on the total battery state of chargeSwitching on a generator at low battery state of charge
9. PV panel configuration10. External control signals
11 Extra Information
Control response timeController
Customer Specific
Devices
External Signals
InstallationLicenseNetworkQuick StartSafety, maintenance and legal noticesSpecificationsStatus LEDs
Toolbox
Troubleshooting
Video tutorialsWiring & connectivity guidelines
Configuration from A to Z8 Local Control ModesSpecial Local Control Modes
Generic logo

Introduction

Switching on a generator at low battery state of charge

This is a special local control mode that is implemented to switch a relay on when the total state of charge of the batteries drops below a configurable value. This will allow a generator to take over and power the loads, and recharge the battery.

Note
Note

The SmartgridOne Controller does not control how much power that generator produces. It only gives a signal to switch the generator on/off.

Configuring the special control mode

Batteries

Make sure that your batteries are added to the SmartgridOne Controller.

Relay device settings

  1. Add the relay through the device wizard:
    1. Go to the 'Devices' page.
    2. Click 'Start wizard'
    3. Choose 'On/off load'
    4. Choose 'Generic'
    5. Choose 'Relay', or 'Ethernet to relay converter', as suited to how the relay is connected.
    6. Scan for and add the relay.
  2. For the relay that is controlled, set the 'Default device state' in the page to the position the relay must take when the mode cannot decide (for example when no battery capacity is known). The mode itself puts the 'Use case' of the relay to 'Direct passthrough of an external control signal' as soon as it is active.

Enabling the special control mode

  1. Go to the 'Settings' tab on the SmartgridOne Controller's interface and click 'Manage special local control modes'.
  2. Click 'Start wizard' under 'Enable a new special local control mode'.
  3. Choose 'Backup genset switch on/off based on the total battery state of charge' and click 'Next'.
  4. Configure the total battery state of charge below which the relay switches on, the state of charge above which it switches off again, and how long (in seconds) it should at least stay on or off after switching. Between the two thresholds the relay keeps its position.
  5. Select the relay and click 'Apply mode to selected devices'.

See for the priority towards other signals, and for pausing or removing the mode.

Tip
Tip

The same mechanism is available for any relay, not only a generator, as .

Last updated September 13, 2026Edit this page

Relay control based on the total battery state of charge

Previous Page

9. PV panel configuration

Next Page

On this page

IntroductionSwitching on a generator at low battery state of chargeConfiguring the special control modeBatteriesRelay device settingsEnabling the special control mode
device settings
Special local control modes
Relay control based on the total battery state of charge