Extra - Battery account for wear and efficiencyExtra - Battery charging scheduleExtra - Battery cost optimization settingsExtra - Battery peak shavingExtra - Device prioritiesExtra - Peak shaving plus (secondary control mode)Extra - Reactive power controlExtra - Self consumption on another meter than the grid meterFull explanationSetting control modes
Special Local Control Modes
Green certificates (Groenestroomcertificaten)Monitoring only (don't control the selected devices)Negative price wind controlPeak Shaving Relay CascadeRelay control based on the total battery state of chargeSwitching on a generator at low battery state of charge
9. PV panel configuration10. External control signals
11 Extra Information
Control response timeController
Customer Specific
Devices
External Signals
InstallationLicenseNetworkQuick StartSafety, maintenance and legal noticesSpecificationsStatus LEDs
Toolbox
Troubleshooting
Video tutorialsWiring & connectivity guidelines
Configuration from A to Z8 Local Control ModesSpecial Local Control Modes

Introduction

What this control mode does

The Negative Price Wind Control special local control mode switches the selected wind inverters off as long as the purchase price of energy on the site is negative, and lets them produce at their nominal power the rest of the time. At negative purchase prices you are paid to consume energy, so every kWh that is produced costs money; a wind turbine, unlike a solar installation, cannot simply be limited to the self-consumption of the site, so it is stopped completely.

  • When the site purchase price is negative, a setpoint of 0 W is sent to all selected inverters.
  • Otherwise, a setpoint equal to the nominal power of each inverter is sent, so the inverters produce at full power.
Note
Note

The purchase price used is the price of the site, as configured in the app under the energy cost settings (the day-ahead price with the scale factor, the surcharge and the grid costs applied). See Pricing parameters. The mode needs energy prices to be available; check the energy prices troubleshooting page if the inverters are never switched off.

Note
Note

This mode is also offered for solar inverters, as it works with any production device. For solar installations the "Cost optimization" working mode is usually the better choice: it limits the production to the self-consumption of the site at negative selling prices, instead of switching everything off.

Configuring the special control mode

Wind inverters

Make sure that the wind inverters are added to the SmartgridOne Controller as production devices, and that their nominal power is set correctly in their device settings.

Enabling the special control mode

  1. Go to the 'Settings' tab of the SmartgridOne Controller's interface and click "Manage special local control modes".
  2. Click "Start wizard" under "Enable a new special local control mode".
  3. Choose "Negative Price Wind Control" and click "Next". The mode has no further inputs.
  4. Select the wind inverters that must be switched off at negative prices, and click "Apply mode to selected devices".

See Special local control modes for the priority towards other signals, and for pausing or removing the mode.

Last updated September 13, 2026Edit this page