SmartgridOne logo
SmartgridOne logo
Accessories
AppCertificates
Configuration from A to Z
1. Link to your account2. Accessing commissioning interface3. Grid limits4. Location / address5. Add grid energy meter6. Add other devices7. Grouping devices
8 Local Control Modes
Extra - Battery account for wear and efficiencyExtra - Battery charging scheduleExtra - Battery cost optimization settingsExtra - Battery peak shavingExtra - Device prioritiesExtra - Peak shaving plus (secondary control mode)Extra - Reactive power controlExtra - Self consumption on another meter than the grid meterFull explanationSetting control modes
Special Local Control Modes
Green certificates (Groenestroomcertificaten)Monitoring only (don't control the selected devices)Negative price wind controlPeak Shaving Relay CascadeRelay control based on the total battery state of chargeSwitching on a generator at low battery state of charge
9. PV panel configuration10. External control signals
11 Extra Information
Control response timeController
Customer Specific
Devices
External Signals
InstallationLicenseNetworkQuick StartSafety, maintenance and legal noticesSpecificationsStatus LEDs
Toolbox
Troubleshooting
Video tutorialsWiring & connectivity guidelines
Configuration from A to Z8 Local Control ModesSpecial Local Control Modes
Generic logo

Introduction

Relay control based on the total battery state of charge

This special local control mode switches one or more relays on when the total state of charge of all the batteries on the site drops below a configurable value, and off again when it rises above another value. It is the general-purpose version of Switching on a generator at low battery state of charge: use it for any load or signal that must follow the state of charge of the batteries, for example a warning lamp, a load that may only run while there is enough energy in the batteries, or a contact towards a building management system.

  • Below the lower threshold, the selected relays are switched on.
  • Above the upper threshold, the selected relays are switched off.
  • Between the two thresholds, the relays keep their position (hysteresis), and a relay stays at least the configured minimum time in the same position.
Note
Note

The total state of charge is the capacity-weighted average of the state of charge of all the batteries of the site.

Note
Note

The timing settings of the relays (minimum and maximum switch on and off times) are ignored in this mode. Only the minimum hold time configured in the mode itself applies.

Warning
Warning

If the total battery capacity is zero (no batteries, or batteries without a configured capacity), the mode cannot decide and puts the relays in their default device state. The mode reports this as an error on the external signals page.

Configuring the special control mode

Batteries

Make sure that your batteries are added to the SmartgridOne Controller.

Relay device settings

  1. Add the relay through the device wizard, see Adding a device: choose 'On/off load', 'Generic', and then 'Relay' or 'Ethernet to relay converter', as suited to how the relay is connected.
  2. In the device settings of the relay, set the 'Default device state' to the position the relay must take when the mode cannot decide. The mode itself puts the 'Use case' of the relay to 'Direct passthrough of an external control signal' as soon as it is active.

Enabling the special control mode

  1. Go to the 'Settings' tab of the SmartgridOne Controller's interface and click "Manage special local control modes".
  2. Click "Start wizard" under "Enable a new special local control mode".
  3. Choose "Relay control based on the total battery state of charge" and click "Next".
  4. Configure the mode:
    • The total battery state of charge (as a percentage) below which the relays should be switched on.
    • The total battery state of charge (as a percentage) above which the relays should be switched off.
    • The minimum time (in seconds) the relays should remain in the same position.
  5. Select the relay(s) and click "Apply mode to selected devices".

See Special local control modes for the priority towards other signals, and for pausing or removing the mode.

Last updated September 13, 2026Edit this page