SmartgridOne logo
SmartgridOne logo
Accessories
AppCertificates
Configuration from A to Z
1. Link to your account2. Accessing commissioning interface3. Grid limits4. Location / address5. Add grid energy meter6. Add other devices7. Grouping devices
8 Local Control Modes
Extra - Battery account for wear and efficiencyExtra - Battery charging scheduleExtra - Battery cost optimization settingsExtra - Battery peak shavingExtra - Device prioritiesExtra - Peak shaving plus (secondary control mode)Extra - Reactive power controlExtra - Self consumption on another meter than the grid meterFull explanationSetting control modes
Special Local Control Modes
Green certificates (Groenestroomcertificaten)Monitoring only (don't control the selected devices)Negative price wind controlPeak Shaving Relay CascadeRelay control based on the total battery state of chargeSwitching on a generator at low battery state of charge
9. PV panel configuration10. External control signals
11 Extra Information
Control response timeController
Customer Specific
Devices
External Signals
InstallationLicenseNetworkQuick StartSafety, maintenance and legal noticesSpecificationsStatus LEDs
Toolbox
Troubleshooting
Video tutorialsWiring & connectivity guidelines
Configuration from A to Z8 Local Control ModesSpecial Local Control Modes
Enervalis logo

Introduction

Peak shaving

The peak shaving relay cascade is a special local control mode that is implemented to switch relays in specific order on or off for peak shaving. This works similar to a last-in-first-out (LIFO) queue.

  • When the grid power drops below the switch-on threshold: The next relay that is currently off will be switched on
  • When the grid power rises above the switch-off threshold: The last relay that is currently on will be switched off

This can be used to control the grid power to remain between the on and off thresholds, with on/off loads.

Order of the relays

The order of the relays is determined by:

  1. The device priority (configureable on the device settings page)
  2. For device of the same priority, devices are switched on in alphabetical order

Configuring the special control mode

Relay device settings

For each of the relays that are controlled, it is recommended to set the 'Use case' to 'Switching a device or circuit' in the device settings page. You should also set the 'Default device state' to whatever is desirable in case there is a problem with the control mode.

Note
Note

Minimum & maximum switch on and wait times: Timing related device settings are ignored in the peak shaving relay cascade control mode. You can however configure a debounce time between switching on and off when enabling the control mode.

Enabling the special control mode

  1. Go to the 'Settings' tab on the SmartgridOne Controller's interface and click 'Manage special local control modes'.
  2. Click 'Start wizard' under 'Enable a new special local control mode'.
  3. Choose 'Peak shaving relay cascade' and click 'Next'.
  4. Set the grid power above which the last active relay is switched off, the grid power below which the next relay is switched on, and the minimum debounce time between switching relays. Leave sufficient room between the two thresholds to avoid relay chatter.
  5. Select the relays and click 'Apply mode to selected devices'.

See Special local control modes for the priority towards other signals, and for pausing or removing the mode.

Last updated September 13, 2026Edit this page