SmartgridOne logo
SmartgridOne logo
Accessories
AppCertificates
Configuration from A to Z
Control response timeController
Customer Specific
Devices
Boiler
Cloud
Energy Meter
ABBAccuenergyAcrelAlgodueAnexoBMR
Carlo Gavazzi
ChargeeChintCloud Meter DataDornscheidt
Eastron
Eniris
FluviusFroniusHagerHomeWizardHuaweiIneproIskra
Janitza
JoulzKaifaKamstrupLandis+GyrLegrandLitiotM-BusMetcomP1ApiPhoenix-ContactPilotSagemcom
Schneider
Self configured energy meterSeneca S604SessyShelly Energy metersSiemensSmappeeSmartgrid-readySocomecSolax
Solis
SunwodaTillquistVictronWeidmüllerYouLessZendure P1 MeterZiv
Ev Charging Station
Gas Meter
Heat Pump
New integrations
Plc
Pv Hybrid And Battery Inverters
Switched Loads
Water Meter
External Signals
InstallationLicenseNetworkQuick StartSafety, maintenance and legal noticesSpecificationsStatus LEDs
Toolbox
Troubleshooting
Video tutorialsWiring & connectivity guidelines
DevicesEnergy Meter

BMR Energy Meters

BMR

Supported Devices

Device TypeModbus TCP (Ethernet)RS485
PLA33✅✅
PLA33RX
BMR PLA33

Figure 1: Front panel of the PLA33 showing buttons like SET, cursor keys, and ESC.

BMR PLA33RX

Figure 2: Front panel of the PLA33RX showing buttons like ESC, cursor keys, and status LEDs for recording and relay outputs.

Wiring

RS485

For RS485 wiring, follow the guidelines for RS485 wiring.

Info
RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
ARS485 ARS485_POSRS485 ATX+
BRS485 BRS485_NEGRS485 BTX-
GNDRS GNDGNDNot availableG
Warning
NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.

Ethernet

For Ethernet wiring, follow the guidelines for Ethernet wiring.


Configuration

RS485 Configuration

To configure RS485 communication on BMR energy meters, follow these steps:

  1. Set the Modbus Address:

    • Access the settings menu by pressing the SET button for 5 seconds.
    • Navigate to the communication menu (P_2) using the cursor keys.
    • Set the Id (unique Modbus address) between 1 and 247.
  2. Set the Baud Rate:

    • In the communication menu (P_2), configure the bd (baud rate) to match your system. Supported baud rates include 9.6 / 19.2 / 38.4 / 57.6 / 115 kBd.
  3. Parity and Stop Bits:

    • Configure PAr (parity) as None, Odd, or Even.
    • Set the St (stop bits) to 1 or 2 as needed.
  4. RS485 Termination:

    • If the meter is the last device on the RS485 bus, add a 120 Ω termination resistor.
Warning
NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.

Ethernet Configuration (PLA33RX Only)

For devices with Ethernet capability:

  1. Ensure the Ethernet cable is properly connected.
  2. Use the Power Monitoring Software (PMS) to configure the IP address, subnet mask, and gateway.
  3. Verify that the Modbus TCP port is set to 502.

Anexo

Anexo Energy Meters

Carlo Gavazzi

Next Page

On this page

Supported DevicesWiringRS485EthernetConfigurationRS485 ConfigurationEthernet Configuration (PLA33RX Only)