SmartgridOne logo
SmartgridOne logo
Accessories
AppCertificates
Configuration from A to Z
Control response timeController
Customer Specific
Devices
Boiler
Cloud
Energy Meter
ABBAccuenergyAcrelAlgodueAnexoBMR
Carlo Gavazzi
ChargeeChintCloud Meter DataDornscheidt
Eastron
Eniris
FluviusFroniusHagerHomeWizardHuaweiIneproIskra
Janitza
JoulzKaifaKamstrupLandis+GyrLegrandLitiotM-BusMetcomP1ApiPhoenix-ContactPilotSagemcom
Schneider
Self configured energy meterSeneca S604SessyShelly Energy metersSiemensSmappeeSmartgrid-readySocomecSolax
Solis
SunwodaTillquistVictronWeidmüllerYouLessZendure P1 MeterZiv
Ev Charging Station
Gas Meter
Heat Pump
New integrations
Plc
Pv Hybrid And Battery Inverters
Switched Loads
Water Meter
External Signals
InstallationLicenseNetworkQuick StartSafety, maintenance and legal noticesSpecificationsStatus LEDs
Toolbox
Troubleshooting
Video tutorialsWiring & connectivity guidelines
DevicesEnergy Meter

Huawei Energy Meters

Huawei

Supported Devices

Device TypeModbus TCP (Ethernet)
Energy Meter via Smartlogger✅
Image 1

The Huawei SmartLogger can be used to read and control energy meters/solar inverters/batteries.

Wiring - Ethernet

For correct ethernet wiring: Follow the the guidelines for ethernet wiring.

Configuration

1. Activating Modbus in the SmartLogger

  1. Surf to the IP address of the SmartLogger.
  2. Login to the SmartLogger (default password: "Changeme").
  3. Change “Link setting” to “Enable (Unlimited)”.
  4. Set “Address mode” to “Communication address”.
  5. Choose the Modbus address of the logger. We recommend that this is different from the addresses of the inverters (see also the next step in the manual).
  6. Click submit.
Image 1
Image 1

2. Device Modbus Addresses

The smartlogger can connect both inverters and energy meters via 3 COM ports. Adding and giving Modbus addresses can be done automatically or not.

However... all Modbus addresses must be different!

Image 1

To adjust this, it is best to first adjust the possible addresses per COM port so that there is no overlap.

Image 1

Then you remove the devices with the same address and add them back with an address different from all other devices.

Image 1