Xantrex

Xantrex Inverters

Supported Devices

The SmartgridOne Controller supports Xantrex inverters that utilize the RS232 communication protocol.

Device TypeVariantsModbus TCP (Ethernet)RS485Curtailment
Xantrex InvertersModels with RS232 interface

Wiring

RS232 Connection

To connect the inverter to the SmartgridOne Controller, you must use the RS232 interface. This is distinct from the RS485 connection used by many other inverters.

  1. Port Selection: Ensure you are connecting to the specific RS232 port on your controller (or using a supported USB-to-RS232 adapter).
  2. Cable: You will typically need a DB9 serial cable.
Pin (DB9)Function
2Rx (Receive)
3Tx (Transmit)
5GND (Ground)
Distance Limit

RS232 cables are designed for short distances. The cable length should generally not exceed 15 meters. If the inverter is located far away from the controller, this connection method may not be reliable.