SmartgridOne logo
SmartgridOne logo
Accessories
AppCertificates
Configuration from A to Z
Control response timeController
Customer Specific
Devices
External Signals
DSO
ORESRESA

AgrolaAutarcoAxpoBEE EnergyCompanion EnergyDexterDiagnostic testsDNO Relay ControlDynamic Energy TradingEdmijElia
Elindus
Energy Flexibility Solutions (EFS)EnervalisEngieEPEX Spot SolarEuropean CommoditiesFleco PowerFlowerFrank EnergieFuseboxGreenchoiceHallostroomImbyKratTrade
Monitoring
Mqtt
New integrationsNext EnergyOpinumParagraph 14a IntegrationPlan-ahead APIPleeviRepoweredScholtTrevionVGT EnergyYuso - Battery ControlYuso - Solar Curtailment
InstallationLicenseNetworkQuick StartSafety, maintenance and legal noticesSpecificationsStatus LEDs
Toolbox
Troubleshooting
Video tutorialsWiring & connectivity guidelines
External SignalsDSO
ORES Logo

Setting up ORES (External Control)

The manual describes the steps to set up ORES External Control on the SmartgridOne Controller.

When setting up this integration, permission is granted to ORES to control the necessary devices.

Supported Devices

Device TypeSupported
Solar Inverters✅
Storage Devices
EV Chargers❌
Caution
Caution

ORES RTU requires a relay and a digital input to work. Please check if your SmartgridOne Controller has an available relay and digital input before setting up this integration. If not, you can use a Relay-Ethernet Converter to connect the ORES RTU to the SmartgridOne Controller.

Caution
Caution

ORES RTU requires a RS485 serial port to work. Please check if your SmartgridOne Controller has an available RS485 port before setting up this integration. If not, you can use a RS485-Ethernet Converter or a RS485-USB Converter to connect the ORES RTU to the SmartgridOne Controller.

Caution
Caution

As ORES RTU is using a RS485 serial connection, the used RS485 port on the SmartgridOne Controller cannot be used for other devices and connections. Please check if your SmartgridOne Controller has an available RS485 port before setting up this integration.

Prerequisites

1. Add the batteries and inverters

Login to the commissioning interface and make sure the devices are added to the SmartgridOne Controller.

2. Check the grid power limits

In the settings, the grid power limits should be set correctly. Click Settings and check the highlighted setting in the image. If necessary, adjust the settings.

3. Add 'ORES' External Signal


1. Click on 'External Signals' in the top menu and click on the 'Start Wizard' button.

Step 1

2. Click on the 'Distribution System Operator' button.

Step 2

3. Click on the 'ORES' button.


4. Select 'ORES RTU Telecontrol' and click 'Next'.


5. Fill in the required information.

  1. RS485 Interface: Select the RS485 serial port to which the ORES RTU is connected. If using a RS485-Ethernet Converter or a RS485-USB Converter, select the corresponding Ethernet or USB port.
  2. Digital Input Device: Select the digital input device to which the ORES RTU is connected, this is used for the ORES RTU to detect if the connection with ORES is active.
  3. Relay Device: Select the relay device to which the ORES RTU is connected, this is used for the ORES RTU to control the connection with ORES. If the relay is activated, the connection with ORES is active and ORES can control the devices. If the relay is deactivated, the connection with ORES is lost and ORES cannot control the devices.
  4. Contractual permanent power: Fill in the contractual permanent power (in kW) that is agreed upon with the grid operator. This is used by our EMS to determine the maximum power that can be injected into the grid if we lose connection with ORES.

6. Select all the available devices, this is required for ORES to be able to control the devices. Then click 'Submit'.


DSO

Previous Page

RESA

Next Page

On this page

Setting up ORES (External Control)Supported DevicesPrerequisites1. Add the batteries and inverters2. Check the grid power limits3. Add 'ORES' External Signal1. Click on 'External Signals' in the top menu and click on the 'Start Wizard' button.2. Click on the 'Distribution System Operator' button.3. Click on the 'ORES' button.4. Select 'ORES RTU Telecontrol' and click 'Next'.5. Fill in the required information.6. Select all the available devices, this is required for ORES to be able to control the devices. Then click 'Submit'.