Raedian charging stations

Raedian

Supported Devices

Device TypeModbus TCP (Ethernet)RS485
Raedian NEO
Raedian NEX
Raedian Charger

Wiring

Ethernet (Raedian NEX)

For correct ethernet wiring: Follow the the guidelines for ethernet wiring.

RS485 (Raedian NEO)

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
A RS485 ARS485_POSRS485 ATX+
B RS485 BRS485_NEGRS485 BTX-
GND RS GNDGNDNot availableG
informacja

Ensure the termination resistor is set correctly if the charger is at the end of the RS485 bus.

Configuration

After the electrical installation is complete, you need to configure the charger using the Raedian App.

  1. Download the Raedian app from the App Store or Google Play Store.
  2. Open the app and register/login.
  3. Add the charging station via Bluetooth/Wi-Fi following the in-app instructions.
  4. Once connected, navigate to the Settings menu (usually represented by a gear icon).

For Raedian NEO (RS485)

To allow the SmartgridOne Controller to control the NEO charger via Modbus RTU:

  1. In the settings menu, look for Communication or Modbus Settings.
  2. Enable Modbus RTU.
  3. Configure the following parameters:
    • Address (Slave ID): Set a unique address (e.g., 1). This must match the configuration in the SmartgridOne Controller.
    • Baud Rate: 9600 (Recommended)
    • Parity: None
    • Data Bits: 8
    • Stop Bits: 1
  4. Save the settings and reboot the charger if prompted.

For Raedian NEX (Modbus TCP)

To allow the SmartgridOne Controller to control the NEX charger via Modbus TCP:

  1. Ensure the charger is connected to the same local network as the SmartgridOne Controller via Ethernet or Wi-Fi.
  2. In the app settings, go to Network Settings.
  3. It is highly recommended to assign a Static IP to the charger to ensure connectivity remains stable after power outages.
    • IP Address: Choose a free IP in your network range (e.g., 192.168.1.50)
    • Subnet Mask: 255.255.255.0
    • Gateway: Your router IP (e.g., 192.168.1.1)
  4. Enable Modbus TCP in the Communication settings.
  5. Ensure the Port is set to 502.