ComPact NSX
The Schneider ComPact NSX is a circuit breaker that can also measure energy. To communicate with the SmartgridOne Controller, it must be equipped with a MicroLogic 5, 6, or 7 trip unit.
Supported Devices
We support the ComPact NSX range with Electronic Trip Units. Choose the driver that matches your device's Modbus profile.
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| ComPact NSXe | ✅ | ✅ |
| ComPact NSXs |
Important: Check your Trip Unit
This driver only works if your breaker has a MicroLogic 5.x, 6.x, or 7.x trip unit.
- Look for the LCD screen: These units always have a digital display.
- Incompatible: Basic thermal-magnetic units (TM-D/TM-G) or MicroLogic 2.x/4.x (dials only) cannot measure energy.

Wiring
You cannot wire directly to the breaker
The ComPact NSX does not have built-in RS485 or Ethernet terminals. You must install an external Interface Module (Gateway) on the DIN rail next to the breaker.
Step 1: The "NSX Cord"
Regardless of your communication method, you need the NSX Cord.
- Open the front cover of the breaker.
- Connect the NSX Cord to the test port on the MicroLogic Trip Unit.
- Route the cable out of the breaker to your DIN rail.
Step 2: Choose your Interface Module
Option A: Modbus RTU (RS485)
Required Part: EcoStruxure IFM Module (Ref: LV434000)
- Snap the IFM module onto the DIN rail.
- Plug the NSX Cord into the bottom of the IFM module.
- Wire the Top Connector (green) to the SmartgridOne Controller RS485 bus:
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| D1 (+) | RS485 A | RS485_POS | RS485 A | TX+ |
| D0 (-) | RS485 B | RS485_NEG | RS485 B | TX- |
| 0V | RS GND | GND | Not available | G |

Option B: Ethernet (Modbus TCP)
Required Part: EcoStruxure IFE Module (Ref: LV434001)
- Snap the IFE module onto the DIN rail.
- Plug the NSX Cord into the bottom of the IFE module.
- Connect a standard Ethernet cable (LAN) from the top RJ45 port to your network switch/router.