DEYE

الأجهزة المدعومة
Device Type | Variants | Modbus TCP (Ethernet) | RS485 | Curtailment |
---|---|---|---|---|
SG04LP3-EU | SUN-5/6/8/10/12K | ❌ | ✅ | ❌ |
SG01LP1-EU | SUN-12/14/16K |
الأسلاك
RS485
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
---|---|---|---|---|
دبوس 1 / Modbus-485_B | RS485 A | RS485_POS | RS485 A | TX+ |
دبوس 2 / Modbus-485_A | RS485 B | RS485_NEG | RS485 B | TX- |
دبوس 3 / GND_485 | RS GND | GND | Not available | G |



الإعداد
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
اذهب إلى “الشاشة الرئيسية” >> “إعدادات النظام” >> “وظيفة متقدمة.”
- يجب أن يكون Modbus SN مضبوطًا على أي رقم بين 1 و 247. لا تحدد 0!! لاحظ أنه إذا كان هناك أجهزة متعددة على ناقل RS485، يجب إعطاء كل جهاز رقمًا فريدًا. هذه هي العنوان.
- يجب أن تكون خانة "Slave" محددة.
- فقط عندما يتم توصيل عداد إضافي مباشرة بالع inverter يجب تحديد خانة “EX_meter For CT”. إذا كان هناك فقط عداد متصل بشكل متوازي مع SmartgridOne Controller يجب إلغاء تحديدها.
- تأكد من أن الإعدادات التالية صحيحة تمامًا: "حد أقصى للتيار عند الشحن"، "حد أقصى للتيار عند التفريغ"، "تيار شبكة الشحن"